EDA-DCLB-125KW

General

Operating Modes: Constant Voltage
Constant Current
Constant Power
Constant Resistance
Multi-Unit Paralleling: Yes
Paralleling Bus: CAN
Weight: 4400 lbs (including transformer)

DC Input Terminals

Nominal Total DC Input Current
463 Amps  dc
Operating Voltage Range 150 – 450 VDC

System AC Outputs

Phases 3-phase
Nominal Continuous Power 125 kW
Nominal Voltage (L-L)  480 V rms
Voltage Operation Range (L-L) +10% – 12%
Nominal Current 167 Amps rms
Frequency Trip Level Range 57 – 63 Hz
Nominal Operation Frequency 60 Hz (59.3 – 60.5 Hz) (adjustable)

Harmonics

Current THD in Grid Mode <3.5%

Environment

Operating Ambient Temp. Range 0 oC to 40oC (32 to 104oF)
Storage Temperature Range -30oC to 60oC (22 to 140oF)
Humidity 0 to 95%
Altitude Derating above 2000m above sea level